Ex Certified Temperature Sensor

Mineral insulated temperature sensor

Marking Ambient Temperature T Class
Ex e IIC T6…T4 -40°C to +80°C T6
-40°C to +95°C T5
-40°C to +130°C T4

Temperature sensor:
W-M-303-ⓐ/ⓑ-ⓒ/FDF-4-A-Ex :Pt100
T-M-303-ⓐ/ⓑ-ⓒ/FDS-Z-1-Ex: Thermocouple K or N type
Max. Measuring current: 10mA
Temperature range: -60°C …+450°C Temporary +550 °C
Diameter of Sensor Probe: 3mm, 6mm, 8mm
Tinned Copper Connection Wires: 0.22mm2
Max. Service Temperature (Connection to MI cable): +130°C
Max. Service Temperature (End sleeve): +105°C

High Temperature range
Standard MI materials AISI 316L
MI-construction, bendable, vibration proof

W-M-303- ⓐ / ⓑ – ⓒ /FDF-4-A-Ex

ⓐ Sensor probe diameter
3: 3mm
6: 6mm
8: 8mm
ⓑ Probe Length (mm), min 30mm
ⓒ -Lead cable Length (mm), min 50mm

 

T-M-303- ⓐ / ⓑ – ⓒ /FDS-Z-1-Ex

ⓐ Sensor probe diameter
3: 3mm
6: 6mm
8: 8mm
ⓑ Probe Length (mm), min 10mm
ⓒ -Lead cable Length (mm), min 50mm

 

Stainless Steel Probe sensor

Marking Ambient Temperature T Class
Ex e IIC T6…T4 -40°C to +80°C T6
-40°C to +95°C T5
-40°C to +130°C T4
40°C to +185°C T3

Temperature sensor: Pt100
Max. Measuring current: 10mA
Operating Temperature: -40°C …+200°C
Diameter of Sensor Probe: 6mm
Tinned Copper Connection Wires: 0.22mm2

Temperature sensor for multiple temperature measurement purposes
Standard MI materials AISI 316L
Pt100, accuracy class A.

ⓐ WT-KAAPELI-6/ ⓑ – ⓒ /TDT-4J-KLA-Ex

ⓐ No. of sensor None : 1, 2X :2
ⓑ Probe Length(mm), min. 30mm
ⓒ Lead cable Length to end sleeve (mm), min. 50mm

 

 

Bayonet temperature sensor

Marking Ambient Temperature T Class
Ex e IIC T6…T4 -40°C to +80°C T6
-40°C to +95°C T5
-40°C to +130°C T4
-40°C to +185°C T3

Temperature sensor: Pt100 x 1, or Pt100 x 2
Max. Measuring current: 10mA
Operating Temperature: -40°C …+200°C
Diameter of Sensor Probe: 6mm, 8mm
Tinned Copper Connection Wires: 0.22mm2

Spring-loaded bayonet sensor for measuring temperature.
Very easy and quick installation due to bayonet connection
Standard MI materials AISI 316L

ⓐ WT-BAJONETTI- ⓑ / ⓒ – ⓓ /TDT-4J-KLA-Ex

ⓐ No. of sensor None : 1, 2X :2
ⓑ Sensor probe diameter
6: 6mm
8: 8mm
ⓒ Probe Length (mm), min. 25mm
ⓓ Lead cable Length to end sleeve (mm), min. 300mm