PYEX-EP-JB

Power Connection, T-Splicing, End Termination
GRP enclosure with plastic gland for heating cable

Details

Protection Type : Ex eb IIC
Applicable heating cables in hazardous location : FBL, FBH, FBX, FBZ
Temperature classification
FBL : T6 (85℃)
FBH : T4 (135℃)
FBX152 / 302 / 452, FBZ152 / 302 / 452 : T3 (200℃)
FBX602, FBZ602 : T2 (300℃)
Enclosure service temperature : -55℃ to 135℃
Plastic heating cable gland (PYEX-EP-PG25) service temperature : -40℃ to 110℃
Max rated voltage 277Vac
Max load current : 50A for PYEX-EP-JB-12 & 16, 100A for PYEX-EP-JB-26
Ingress Protection : IP65 (when assembled with heating cables)
Enclosure Material : Glassfibre reinforced polyester / UV stabilized
Impact Resistance : 7J
Flammability : Self-extinguishing UL 94/V-0
Color : Graphite Black
Gasket and Seal : Flame-proof silicone rubber
Maximum power conductor cross-section : 10mm²
Thread for power cable entry : Max. M25, PF3/4, NPT3/4-14
Approval : ATEX, IECEx
Reference standards : IEC60079-0, IEC60079-7, IEC60079-30-1

The PYEX-EP-JB is an Ex certified GRP enclosure system designed and manufactured to meet all
requirements from relevant international standards for industrial heat tracing cable system
especially for hazardous location such as petrochemical plant,gas plant, ship and off-shore
facility and utilizes an Ex certified GRP enclosure with plastic gland for self-regulating heating
cable’s connection and termination.

PYEX-EP-JB   –    12      –       P

ⓐ                                ⓑ              ⓒ

 

ⓐ Model

ⓑ Enclosure size
12: 120x120x90 box
16: 160x160x90 box
26: 260x160x90 box

ⓒ Function
P: Power connection,
T: T-Splicing
E: End termination

 

 

 

Product Image

Components