PYEX-EP-JBS

Power Connection, T-Splicing, End Termination
GRP enclosure with stainless steel pipe-mount

Details

Protection Type : Ex eb IIC
Applicable heating cables in hazardous location : FBL, FBH, FBX, FBZ
Temperature classification
FBL : T6 (85℃)
FBH : T4 (135℃)
FBX152 / 302 / 452, FBZ152 / 302 / 452 : T3 (200℃)
FBX602, FBZ602 : T2 (300℃)
Enclosure service temperature : -55℃ to 135℃
Plastic heating cable gland (PYEX-EP-PG25) service temperature : -40℃ to 110℃
Max rated voltage 277Vac
Max load current : 50A for PYEX-EP-JB-12 & 16, 100A for PYEX-EP-JB-26
Ingress Protection : IP65 (when assembled with heating cables)
Enclosure Material : Glassfibre reinforced polyester / UV stabilized
Impact Resistance : 7J
Flammability : Self-extinguishing UL 94/V-0
Color : Graphite Black
Gasket and Seal : Flame-proof silicone rubber
Maximum power conductor cross-section : 10mm²
Thread for power cable entry : Max. M25, PF3/4, NPT3/4-14
Approval : ATEX, IECEx
Reference standards : IEC60079-0, IEC60079-7, IEC60079-30-1

Protection Type : Ex eb IIC
Applicable heating cables in hazardous location : FBL, FBH, FBX, FBZ
Temperature classification
FBL : T6 (85℃)
FBH : T4 (135℃)
FBX15x / 30x / 45x, FBZ15x / 30x / 45x : T3 (200℃)
FBX60x, FBZ60x : T2 (220℃)
Enclosure service temperature : -55℃ to 135℃
Stainless steel pipe-mount service temperature on the pipe : -50℃ to 300℃
Max rated voltage 277Vac
Max load current : 30A for PYEX-EP-JBS-12, 16 & 26
Ingress Protection : IP64 (when assembled with heating cables)
Enclosure Material : Glassfibre reinforced polyester / UV stabilized
Impact Resistance : 7J
Flammability : Self-extinguishing UL 94/V-0
Color : Graphite Black
Gasket and Seal : Flame-proof silicone rubber
Maximum power conductor cross-section : 10mm²
Thread for power cable entry : Max. M25, PF3/4, NPT3/4-14
Approval : ATEX, IECEx
Reference standards : IEC60079-0, IEC60079-7, IEC60079-30-1

PYEX-EP-JBS   –    12      –       P

ⓐ                                ⓑ              ⓒ

 

ⓐ Model

ⓑ Enclosure size
12: 120x120x90 box
16: 160x160x90 box
26: 260x160x90 box

ⓒ Function
P: Power connection,
T: T-Splicing
E: End termination

 

 

 

Product Image

Components

Seal Selection and Applicable Heaters