PYEX-EP-JBP
Power Connection, T-Splicing, End Termination
GRP enclosure with plastic pipe-mount
Details
Protection Type : Ex eb IIC
Applicable heating cables in hazardous location : FBL, FBH, FBX, FBZ
Temperature classification
FBL : T6 (85℃)
FBH : T4 (135℃)
FBX15x / 30x / 45x, FBZ15x / 30x / 45x : T3 (200℃)
FBX60x, FBZ60x : T2 (220℃)
Enclosure service temperature : -55℃ to 135℃
Plastic pipe-mount service temperature on the pipe :-50℃ to 200℃
Max rated voltage 277Vac
Max load current : 50A for PYEX-EP-JBP-12 & 16, 100A for PYEX-EP-JBP-26
Ingress Protection : IP66 (when assembled with heating cables)
Enclosure Material : Glassfibre reinforced polyester / UV stabilized
Impact Resistance : 7J
Flammability : Self-extinguishing UL 94/V-0
Color : Graphite Black / Pipe-mount : PPS
Gasket and Seal : Flame-proof silicone rubber
Maximum power conductor cross-section : 10mm²
Thread for power cable entry : Max. M25, PF3/4, NPT3/4-14
Gasket and Seal : Flame-proof silicone rubber
Approval : KCs, ATEX, IECEx
Reference standards : IEC60079-0, IEC60079-7, IEC60079-30-1
The PYEX-EP-JBP is an Ex certified GRP enclosure with engineering plastic pipe-mount system
designed and manufactured to meet all requirements from relevant international standards for
industrial heat tracing cable system especially for hazardous location such as petrochemical
plant, gas plant,ship and off-shore facility and utilizes an Ex certified GRP enclosure with plastic
pipe-mount for self-regulating heating cable’s connection and termination.
PYEX-EP-JBP – 12 – P
ⓐ ⓑ ⓒ
ⓐ Model
ⓑ Enclosure size
12: 120x120x90 box
16: 160x160x90 box
26: 260x160x90 box
ⓒ Function
P: Power connection,
T: T-Splicing
E: End termination
![]()

![]()
![]()
Product Image
Components
Seal Selection and Applicable Heaters