PYEX-EP-JB-LE
End termination, Monitoring
GRP enclosurewith signal lamp & plastic gland for heating cable
Details
Protection Type : Ex d eb IIC
Applicable heating cables in hazardous location : FBL, FBH, FBX, FBZ
Temperature classification
FBL : T6 (85℃)
FBH : T4 (135℃)
FBX15x / 30x / 45x, FBZ15x / 30x / 45x : T3 (200℃)
FBX60x, FBZ60x : T2 (220℃)
Enclosure service temperature : -55℃ to 135℃
Plastic heating cable gland (PYEX-EP-PG25) service temperature : -40℃ to 110℃
Max rated voltage 277Vac
LED signal lamp
Rated voltage: 20~ 250Vac
Power consumption: ≤1W
Color: Green, Red, Yellow, Blue, White
Max load current : 50A for PYEX-EP-JB-12 & 16, 100A for PYEX-EP-JB-26
Ingress Protection : IP65 (when assembled with heating cables)
Enclosure Material : Glassfibre reinforced polyester / UV stabilized
Impact Resistance : 7J
Flammability : Self-extinguishing UL 94/V-0
Color : Graphite Black
Gasket and Seal : Flame-proof silicone rubber
Maximum power conductor cross-section : 10mm²
Thread for power cable entry : Max. M25, PF3/4, NPT3/4-14
Approval : ATEX, IECEx
Reference standards : IEC60079-0, IECEx60079-1, IEC60079-7, IEC60079-30-1
The PYEX-EP-JB-LE is designed and manufactured to meet all requirements of relevant
standards for industrial heat tracing cable system in hazardous location such as petrochemical
plant, gas plant, ship and off-shore facility and utilizes an Ex certified GRP enclosure with plastic
gland for self-regulating heating cable’s termination. For monitoring an Ex certified LED signal
lamp is installed on the lid of GRP enclosure.
PYEX-EP-JB – 12 – LE
ⓐ ⓑ ⓒ
ⓐ Model
ⓑ Enclosure size
12: 120x120x90 box
16: 160x160x90 box
26: 260x160x90 box
ⓒ Function
LE: End termination with signal lamp
![]()

![]()
Product Image
Components